11.12 Surge Suppression Unit (SSU)
11-55
SELECTING PERIPHERAL EQUIPMENT
Chap 11
11.12 Surge Suppression Unit (SSU)
■ Dimensions
• 100 m spec: SSU 100TA-NS
■ Effects of surge suppression units (voltage waveform between motors)
■ Basic specifications
200 V and 400 V classes; PWM converter is applicable.
Up to 75 kW (90 kW or larger requires customized service.)
Up to 15 kHz (Cannot be used at 16 kHz.)
Ambient temperature: -20 to +40°C, relative humidity: 85% RH or below,
vibration: 0.7 G or less, Installation: horizontally
Dielectric strength voltage
If the drive wire for the motor is long, an extremely low surge voltage (micro surge) occurs at the
wire end connected to the motor. Surge voltage causes motor degradation, insulation
breakdown, or i
ncreased noises. The surge suppression unit (SSU) suppresses the surge
voltage. It features the connectivity for all inverter capacities and easy wiring work.
Surge suppression mechanism
• Motor/inverter capacity: 3.7 kW
• Running status: No-load
• Wiring length: 50 m
• Power supply voltage:
Three-phase 400 V
• Motor/inverter capacity: 75 kW
• Running status: No-load
• Wiring length: 100 m
• Power supply voltage:
Three-phase 400 V