5.3 Description of Function Codes
5-248
5.3.10 U codes (Customizable logic operation)
The customizable logic function allows the user to form a logic or operation circuit for digital/analog input/output
signals, customize those signals arbitrarily, and configure a simple relay sequence inside the inverter.
In the customizable logic, one step (component), depending on the type, is composed of:
(1) Digital 2 inputs, digital 1 output + logical operation (including timer)
(2) Analog 2 inputs, analog 1 output/digital 1 output + numerical operation
(3) Analog 1 input, digital 1 input, analog 1 output + numerical operation, logical operation
and a total of 200 steps can be used to configure a sequence.
■ Modes
Item Modes
Terminal command Digital 2 inputs Analog 2 inputs Analog 1 input
Digital 1 input
Operation block Logical operation,
counter, etc.: 13 types
Timer: 5 types
Numerical operation,
comparator, limiter,
etc.: 25 types
Selector, hold, etc.:
12 types
Output signal Digital 1 output Analog 1 output/
Digital 1 output
Analog 1 output
Number of steps 200 steps
Customizable logic output signal 10 outputs
Customizable logic processing
time
2 ms (max. 10 steps), 5 ms (max. 50 steps),
10 ms (max. 100 steps), 20ms (max. 200 steps)
Can be selected with a function code.
Customizable logic cancellation
command “CLC”
Allows to stop all the customizable logic operations by assigning “CLC” to
a general-purpose input terminal and turning it ON.
It is used when you want to deactivate the customizable logic temporarily.
Customizable logic timer
cancellation command “CLTC”
Resets the timer, counter and all the previous values used in customizable
logic by assigning “CLTC” to a general-purpose input terminal and turning
it ON. It is used when a customizable logic is changed or if you want to
synchronize it with external sequence.