12.1 Standard Model
12-7
SPECIFICATIONS
Chap 12
12.1.3 HND-mode inverters for general load
■ Standard-model, Three-phase 200 V (230 V) class series (HND-mode: 0.2 kW to 5.5 kW)
Item Specifications
Type (FRN_ _ _ _E2S-2) 0001 0002 0004 0006 0010 0012 *10 0020 *10
Nominal applied motor (kW) [HP]
(Output rating)
0.2
[1/4]
0.4
[1/2]
0.75
[1]
1.1
[1.5]
2.2
[3]
3.0
[4]
5.5
[7.5]
Output ratings
Rated capacity (kVA) *2
0.5
[0.5]
0.8
[0.8]
1.3
[1.4]
2.3
[2.4]
3.7
[3.8]
4.6
[4.8]
7.5
[7.8]
Rated voltage (V) *3 Three-phase 200 to 240 V (with AVR function)
Rated current (A) *4 1.3 2.0 3.5 6.0 9.6 12 19.6
Overload capability 120%-1 min
Input power
Voltage, frequency Three-phase 200 to 240 V, 50/60 Hz
Allowable voltage/frequency
Voltage: +10 to -15% (Interphase voltage unbalance: 2% or less) *6,
Frequency: +5 to -5%
Rated input current *7
(w/o DCR) (A)
1.8 2.6 4.9 6.7 12.8 17.9 31.9
(with DCR) (A) 0.93 1.6 3.0 4.3 8.3 11.7 19.9
Required capacity
(with DCR) (kVA) *8
0.4 0.6 1.1 1.5 2.9 4.1 6.9
Braking
Torque (%)
75% 53% 68% 48% 29% 27%
DC braking
Braking starting frequency: 0.0 to 60.0 Hz, Braking time: 0.0 to 30.0 s,
Braking level: 0 to 80% ( Type FRN0012E2S-2 and FRN0020E2S-2 : 0 to 60% )
Braking transistor Built-in as standard
Minimum resistance value (Ω)
100 40 33
Braking resistor Separately mounted option
DC reactor (DCR) Separately mounted option
Applicable safety standards IEC/EN61800-5-1: 2007
Enclosure (IEC60529) IP20, UL open type
Cooling method Natural cooling Fan cooling
Weight / Mass (kg) [lbs]
0.5
[1.1]
0.5
[1.1]
0.6
[1.3]
0.8
[1.8]
1.5
[3.3]
1.5
[3.3]
1.8
[4.0]
Note: A box () in the above table replaces GA, GB or C depending on the model.
*1 Fuji 4-pole standard motor
*2 Rated capacity is calculated assuming the rated output voltage as 220 V (230 V).
*3 Output voltage cannot exceed the power supply voltage.
*4 Setting the carrier frequency (F26) to the following value or above requires current derating.
HND/ND spec. of types FRN0001E2■-2 to FRN0020E2■-2 : 4 kHz,
If reduction is necessary, for details, refer to Chapter 10, Section 10.4.2 "Guideline for selecting inverter drive
mode and capacity."
*6
67 ×
(V) voltage average phase-Three
(V) voltage Min. - (V) voltage Max.
=(%) unbalance Voltage
(IEC 61800-3)
If the unbalance ratio is 2% to 3%, use an optional AC reactor (ACR).
*7 This specification is an estimated value to be applied when the power supply capacity is 500 kVA (Inverter
capacity × 10 when the capacity exceeds 50 kVA) and the power supply with %X = 5% is connected.
*8 This specification applies when a DC reactor (DCR) is used.
*9 Average braking torque for the motor running alone. It depends on the efficiency of the motor.
*10 Types FRN0012E2■-2 and FRN0020E2■-2 are ND spec; allowable ambient temperature 40°C (+104°F)
or less. The rated output current is decreased 1% for every 1°C (1.8°F) when ambient temperature is +40°C
(+104°F) or more.