3.3 Running Mode
3-5
OPERATION USING THE KEYPAD
Chap 3
3.3 Running Mode
3.3.1 Monitoring the running status
In Running mode, the 17 items listed below can be monitored. Immediately after the inverter is turned on, the
monitor item specified by function code E43 is displayed. Press the key to switch between monitor items.
Table 3.3-1 Monitoring Items
Monitor items
Display
sample on
the LED
monitor *
1
LED indicator
: on, : off
Unit Meaning of displayed value
Function
code data
for E43
Speed monitor
Function code E48 specifies what to be displayed on the LED monitor and LED
indicators.
0
Output frequency 1
(before slip
compensation)
5*00
Hz A kW Hz Frequency actually being output (E48 = 0)
Output frequency 2
(after slip
compensation)
5*00
Hz A kW Hz Frequency actually being output (E48 = 1)
Reference frequency
5*00
Hz A kW Hz Reference frequency being set (E48 = 2)
Motor speed
1500
Hz A kW r/min
P01
120
× (Hz)frequency Output
(E48 = 3)
Load shaft speed
30*0
Hz A kW r/min
Output frequency (Hz) × E50
(E48 = 4)
Line speed
30*0
Hz A kW m/min
Output frequency (Hz) × E50
(E48 = 5)
Constant feeding rate
time
50
Hz A kW min
E39 × (Hz)frequency Output
50
(E48 = 6)
Speed (%)
5*0
Hz A kW %
100 ×
frequency Maximum
frequency Output
(E48 = 7)
Output current
1"34
Hz A kW A Current output from the inverter in RMS 3
Input power
1*25
Hz A kW kW Input power to the inverter 9
Calculated torque *
2
50
Hz A kW % Motor output torque (Calculated value) 8
Output voltage *
3
200u
Hz A kW V Voltage output from the inverter in RMS 4
Motor output *
4
)85
Hz A kW kW Motor output (kW) 16
Load factor *
5
50;
Hz A kW %
Load factor of the motor in % as the rated
output being at 100%
15
PID command *
6
, *
7
1*0*
Hz A kW
PID command/feedback amount converted to
a physical quantity of the object to be
controlled (e.g. temperature)
Refer to function codes J106 and J107 for
details.
10
*
6
, *
8
PID feedback amount
)0*
Hz A kW
12
PID output *
6
, *
7
10**
Hz A kW %
PID output in % as the maximum frequency
(F03) being at 100%
14
Analog input monitor *
9
8"00
Hz A kW
An analog input to the inverter in a format
suitable for a desired scale.
Refer to the following function codes.
Terminal [12]: C59, C60
Terminal [C1] (C1 function): C65, C66
Terminal [C1] (V2 function): C71, C72
17
Current position pulse
765
432!
Hz A kW Pulse
Upper and lower digits are displayed
alternately.
21
Positioning deviation
pulse
765
432!
Hz A kW Pulse
Upper and lower digits are displayed
alternately.
22
Torque current *
10
48
Hz A kW %
Torque current command value or calculated
torque current
23
Magnetic flux *
10
command
50
Hz A kW % Magnetic flux command value 24
Input watt-hour
10*0
Hz A kW kWh
Input watt-hour (kWh)
100
25
Timer *
11
50
Hz A kW s Remaining time for timer operation 13