4.10 Selecting a Frequency Command Source
4-30
4.10 Selecting a Frequency Command Source
The frequency command source by factory default is the keypad (
/ keys). This section provides the frequency
command setting procedures using the frequency command sources of the keypad, external potentiometer, and
frequency selection terminal commands.
4.10.1 Setting up a frequency command from the keypad
Follow the procedure given below.
(1) Configure the function codes as listed below.
Function
code
Name Function code data Factory default
F01 Frequency Command 1 0: Keypad ( / keys) 0
When the inverter is in Programming or Alarm mode, frequency command setting with / keys
is disabled. To enable it, switch to Running mode.
If any of higher priority frequency command sources (multistep frequency
commands and
frequency
commands via communications link) is specified, the inverter may run at an unexpected
frequency.
(2) Press the / key to display the current frequency command on the LED monitor. The least significant digit
blinks.
(3) To change the frequency command, press the / key again.
When you start specifying the frequency command with the / key, the least significant digit on the
display blinks; that it, the cursor is located in the least significant digit. Holding down the / key changes
data in the least significant digit and generates a carry, while the cursor remains in the least significant digit.
(4) To save the new setting into the inverter's memory, press the
key.
For details on how to modify the function code data, see Chapter 3 3.4.1 Setting up function codes Data
Setting:
!f__
through
!o__
”.”
4.10.2 Setting up a frequency command with an external potentiometer
Follow the procedure given below.
(1) Configure the function codes as listed below.
Function
code
Name Function code data Factory default
F01 Frequency Command 1
1: Analog voltage input to terminal [12]
(0 to ±10 V)
0
If terminal [FWD] and [REV] are ON (short-circuited), the F01 data cannot be changed. First turn
those terminals OFF and then change the F0
1 data.
(2) Connect an external potentiometer to terminals [11] through [13] of the inverter.
(3) Rotate the external potentiometer to apply voltage to terminal [12] for a frequency command input.
For precautions in wiring, refer to Chapter 2 INSTALLATION AND WIRING.”
For details on how to modify the function code data, see Chapter 3 3.4.1 Setting up function codes Data
Setting:
!f__
through
!o__
”.”