EasyManua.ls Logo

Fuji Electric FRENIC-Ace series - Motor Stalls During Acceleration

Fuji Electric FRENIC-Ace series
788 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.5 When Codes Other Than Alarm Codes and Light Alarm Indication (
l-al
) are Displayed
6-31
TROUBLESHOOTING
Chap 6
[ 10 ] Motor stalls during acceleration
Possible Causes Check and Measures
(1) The acceleration time was too
short.
Check the data of acceleration time (F07, E10, E12, E14, H57, H58).
Extend the acceleration time.
(2) Moment of inertia of load is
large.
Measure the inverter output current.
Reduce the moment of inertia of the load.
Increase the inverter capacity.
(3) Voltage drop of wiring is large. Check the terminal voltage of motor.
Increase the diameter or shorten the distance of wirings between
the inverter and motor.
(4) Load torque of load is large. Measure the inverter output current.
Reduce the load torque of load.
Increase the inverter capacity.
(5) Torque generated by the motor
was insufficient.
Check whether the inverter can make the motor rotate when torque
boost related functions (F09, H51) are increased.
Change the setting of F09, F37, H51. Increase F09, H51.