4.4 Destination setting
4-4
4.4 Destination setting
For inverter type FRN****E2S/E2E-2G/4G/7G (FRENIC-Ace Global Model), the destination must be set first
after the initial power supply. Without setting the destination, the function code cannot be changed. The inverter
cannot be operated either. By setting the destination, basic function codes such as rated voltage, rated frequency,
etc. are initialized to general values in each region (Table 4.4-1). If the destination value setting is changed after the
initial destination setting, it can be changed with
(des
in the program mode menu or function code H101. If the
destination is reset by
(des
, all function codes are initialized to the factory defaults. If the destination is set by
H101, only the function codes in Table 4.4-1 are initialized to the values in Table 4.4-1. The destination can be
selected from the regions of Japan, Asia, China, Europe, Americas and Korea.
If the function code set including the destination setting function code (H101) is copied with the data copy function or
the FRENIC loader, manual destination setting is not required.
Set the initial destination as shown below. Refer to Figure 4.4-1 on the page 4-5.
(1) With
(des
displayed, press key first.
(2)
asia
(Asian region) is displayed first. For other regions, while pressing key and press key or key
to select the destination.
(3) After selecting the destination,
saue
is displayed by pressing key and the destination setting is
completed. Then,
*.00
is displayed.
Table 4.4-1 Initial value for each destination
Destination Asia China Europe Americas Korea Japan
LED display asia chn eU amer kor jpn
H101:Destination 2 3 4 5 7 1
F03:Maximum output frequency 1 60.0Hz (200V)
50.0Hz 50.0Hz 60.0Hz 60.0Hz
60.0Hz
F04:Base frequency 1 50.0Hz
F05:Rated voltage at base
frequency 1
220/415V 200/380V 200/400V 230/460V 220/380V 200/400V
F06:Maximum output voltage 1
F14:Restart mode after momentary
power failure (Mode selection)
1 1 0 0 1 1
F44:Current limiter (Level) 130% 130% 130% 130% 130% 180/160%
E31:Frequency detection 1 (Level)
60.0Hz (200V)
50.0Hz 50.0Hz 60.0Hz 60.0Hz
60.0Hz
E36:Frequency detection 2 (Level)
E54:Frequency detection 3 (Level) 50.0Hz
P99:Motor 1 selection 0 0 0 1 0 0
H96:STOP key priority/ Start check
function
0 0 0 3 0 0
A01:Maximum output frequency 2 60.0Hz (200V)
50.0Hz 50.0Hz 60.0Hz 60.0Hz
60.0Hz
A02:Base frequency 2 50.0Hz
A03:Rated voltage at base
frequency 2
220/415V 200/380V 200/400V 230/460V 220/380V 200/400V
A04:Maximum output voltage 2
A39:Motor 2 selection 0 0 0 1 0 0
K01:Multifunction keypad TP-A1
(Language selection)
1 6 1 1 1 0