11.22 Digital I/O interface card (OPC-DIO)
11-68
11.22 Digital I/O interface card (OPC-DIO)
This interface card can provide following features to the FRENIC-Ace series.
(1) Available to set frequency point with binary (8,12bit) or BCD code.
(2) Available to monitor with binary (8bit) code.
(3) Available to extend the digital input terminals as I1 to I13.
(4) Available to extend the transistor output terminals as O1 to O8.
Note: Two or more communication cards cannot be mounted simultaneously. And this card requires a mounting
adapter; refer to Section 11.19 .
Applicable ROM version
This card is applicable to inverters with a ROM version 0300 or later.
Table 11.22-1 Terminal functions
Symbol Name Function
I1 to I13 Signal input
Terminals for setting input
Extended digital input signals
M1 External power supply connect External power supply connect
CM
Common of input
The terminal CM is isolated to terminal M2.
Common terminal for setting input
O1 to O8 Output
Terminals for output monitor
Extended transistor output signals
M2
Common of Output
The terminal M2 is isolated to terminal CM.
Common terminals for output monitor
Output terminal
Figure 11.22-1 Terminal allocation on the DIO option interface card
Table 11.22-2 Electrical Specifications
Terminal Symbol Item
Specification
min. max.
I1 to I13
Operating voltage (SINK)
ON level 0V 2V
OFF level 22V 27V
Operating voltage (SOURCE)
ON level 22V 27V
OFF level 0V 2V
Operating current at ON. 2.5mA 4.5mA
Allowable leakage current at OFF - 0.5mA
O1 to O8
Operating voltage
At ON level - 2V
At OFF level - 27V
Maximum current at ON - 50mA
Leakage current at OFF - 0.1mA
Table 11.22-3 Connecting Method input terminals