5.2.4 Motor constants
[ 1 ] When Fuji standard motor 8-series, or other motors are selected by motor selection
(Function code P99/ A39 = 0 or 4)
■ 3-phase 200V class, Fuji standard motor
Motor rated
capacity setting
range (kW)
P02/A16
Applicable
motor
capacity
(kW)
Rated
current
(A)
P03/A17
*1
No-load
current
(A)
P06/A20
*1
%R1 (%)
P07/A21
*1
%X (%)
P08/A22
*1
Rated slip
frequency
P12/A26
Iron loss
factor 1
P13/A27
Starting mode
(Auto search
delay time 2)
H46
0.01 to 0.09 0.06 0.44 0.40 13.79 11.75 1.77 14.00
0.5
0.10 to 0.19 0.1 0.68 0.55 12.96 12.67 1.77 14.00
0.20 to 0.39 0.2 1.30 1.06 12.95 12.92 2.33 12.60
0.40 to 0.74 0.4 2.30 1.66 10.20 13.66 2.40 9.88
0.75 to 1.49 0.75 3.60 2.30 8.67 10.76 2.33 7.40
1.50 to 2.19 1.5 6.10 3.01 6.55 11.21 2.00 5.85
2.20 to 3.69 2.2 9.20 4.85 6.48 10.97 1.80 5.91 0.6
3.70 to 5.49 3.7 15.00 7.67 5.79 11.25 1.93 5.24 0.8
5.50 to 7.49 5.5 22.50 11.00 5.28 14.31 1.40 4.75 1.0
7.50 to 10.99 7.5 29.00 12.50 4.50 14.68 1.57 4.03 1.2
11.00 to 14.99 11 42.00 17.70 3.78 15.09 1.07 3.92 1.3
15.00 to 18.49 15 55.00 20.00 3.25 16.37 1.13 3.32
2.0
18.50 to 21.99 18.5 67.00 21.40 2.92 16.58 0.87 3.34
22.00 to 29.99 22 78.00 25.10 2.70 16.00 0.90 3.28
30.00 to 36.99 30 107.0 38.90 2.64 14.96 0.80 3.10 2.3
37.00 to 44.99 37 130.0 41.50 2.76 16.41 0.80 2.30
2.5
45.00 to 54.99 45 156.0 47.50 2.53 16.16 0.80 2.18
55.00 to 74.99 55 190.0 58.60 2.35 16.20 0.94 2.45 2.6
75.00 to 89.99 75 260.0 83.20 1.98 16.89 0.80 2.33 2.8
90.00 to 109.9 90 310.0 99.20 1.73 16.03 0.80 2.31 3.2
110.0 or above 110 376.0 91.20 1.99 20.86 0.66 1.73 3.5
*1: F05: The value for the model, in which the rated voltage at base frequency 1 is not 200V, becomes the