11.13 Output Circuit Filters (OFLs)
11-56
11.13 Output Circuit Filters (OFLs)
Insert an OFL in the inverter power output circuit to:
Suppress the surge voltage at motor terminals
This protects the motor from insulation damage caused by the application of high voltage surge currents from
the 400 V class series of inverters.
Suppress leakage current from the output lines
This reduces the leakage current from long power feed lines. (The maximum wiring length must be 400 m.)
Minimize radiation and induction noise from the output lines
An OFL effectively suppresses noise from long lines such as wiring at plants.
Output circuit filter (OFL)
Inverter
M
Motor
W
V
U
W
V
U
Z
Y
X
Figure 11.13-1 External View of Output Circuit Filter (OFL) and Connection Example
Table 11.13-1 Output Circuit Filter (OFL)
OFL--4A
Power supply
voltage
Nominal applied motor
(kW)
Filter type Rated current (A) Generated loss (kW)
Three-phase 400V
0.4
OFL-0.4-4A
1.5
80
0.75
OFL-1.5-4A 3.7 105
1.5
2.2
OFL-3.7-4A 9 210
3.7
5.5
OFL-7.5-4A 18 190
7.5
11
OFL-15-4A 30 320
15
18.5
OFL-22-4A 45 350
22
30 OFL-30-4A 60 570
37 OFL-37-4A 75 610
45 OFL-45-4A 91 810
55 OFL-55-4A 112 910
75 OFL-75-4A 150 1200
90 OFL-90-4A 176 1360
110 OFL-110-4A 210 1410
132
OFL-132-4A
253
1800
160
OFL-160-4A
304
2210
200 OFL-200-4A 377 2520
220 OFL-220-4A 415 2590
250
OFL-280-4A 520 3570
280
315 OFL-315-4A 585 3290
355 OFL-355-4A 650 3320