Appendix B Japanese Guideline for Suppressing Harmonics by Customers Receiving High
Voltage or Special High Voltage (General-purpose inverter)
Appendix-16
[ 3 ] Examples of calculation
(1) Equivalent capacity
Example of loads
Input capacity and
No. of inverters
Conversion factor Equivalent capacity
[Example (1)] 400V, 3.7kW,10 units
w/- AC/DC reactor
4.61 kVA × 10 units K32=1.4 4.61101.4= 64.54 kVA
[Example (2)] 400V, 1.5kW, 15 units
w/- AC reactor
2.93 kVA × 15 units K34=1.8 2.93151.8= 79.11 kVA
Refer to Table B-2. Refer to Table B-3.
(2) Harmonic current for every harmonic order
Example 1: 400V, 3.7kW, 10 units (w/- AC reactor), maximum availability factor: 0.55
6.6kV side
fundamental current (mA
823.5 314.2
Refer to Table B-4 and
Table B-6.
Refer to Table B-5.
Example 2: 400V, 3.7kW, 15 units (w/- AC/DC reactor), maximum availability factor: 0.55
6.6kV side
fundamental current (mA