9.2 CANopen Communication
9-10
9.2 CANopen Communication
9.2.1 Modes
Table 9.2-1 lists the CANopen modes. The CANopen mode will apply to the items not contained in the table below.
Table 9.2-1 CANopen Mode
Item Modes Remarks
Physical layer CAN (ISO11898) (High speed)
Node ID 1 to 127 Can be set by the inverter
function code y21 / o31
Baud rate 20k, 50k, 125k, 250k, 500k, 800k, 1Mbit/s Can be set by the inverter
function code y24 / o32
Maximum cable
length
Refer to Table 9.2-3 Twisted pair cable (shielded)
No. of connection
units
30 (MAX) Loop bus
Protocol version Standard format (2.0A)
Profile Compliant with the following profiles;
CiA DS 301 Ver.4.02
CiA DSP 402 Ver.2.0 Velocity Mode
PDO Receive PDO and Transmit PDO, three types each
PDO assignment cannot be changed
Refer to Section 9.2.5
SDO Supports one Server SDO Refer to Section 9.2.6
Other services Network Management(NMT) Start_Remote_Node,
Stop_Remote_Node, Enter_Pre-Operational,
Reset_Communication, Reset_Node
Heartbeat (Producer and Consumer)
Node Guarding
Emergency (EMCY)
Refer to Section 9.2.7
The built-in CANopen and option communication cards cannot be used at the same time.
The built
-in CANopen is not supported in FRN-E2
-2/4GB, -4C.