Appendix D Inverter Generating Loss
Appendix-21
Appendix D Inverter Generating Loss
The table below lists the inverter generating loss.
Unit: W
Carrier frequency (Functional code:F26)
3-phase 200V
FRN0001E2■-2
- - 19 22 16 18
FRN0002E2■-2
- - 29 34 23 27
FRN0004E2■-2
- - 47 51 35 39
FRN0040E2■-2
- - 370 460 280 360
FRN0056E2■-2
- - 560 670 440 540
FRN0069E2■-2
- - 620 830 520 700
3-phase 400V
FRN0002E2■-4
33 32 32 56 30 52
FRN0004E2■-4
57 50 50 93 40 72
FRN0037E2■-4
460 390 390 630 300 490
FRN0044E2■-4
470 410 410 750 330 600
FRN0059E2■-4
710
510 510 870 440 770
FRN0203E2■-4
2250 1950 1950 2250 1600 2150
FRN0240E2■-4
2700 2250 2250 2550 1900 2600
FRN0290E2■-4
3200 2700 2700 3050 2300 3050
FRN0011E2■-7
- - - - 100 130
Note 1: The maximum set value (max. carrier) differs depending on specification. For details please refer to
Chapter 5 “FUNCTION CODE” F26.
Note 2: When ND/HD specification units are operated at maximum carrier, reduce output to 60% of rated current.
At that setting, generated losses will be at same level as the factory shipment value.
(*1) ND spec.