When the variable torque V/f pattern is selected (F37 = 0 or 3), the output voltage may be low at a low
frequency zone, resulting in insufficient output torque, depending on the characteristics of the motor and
load. In such a case, i
H50 = 1/10 of the base frequency
H51 = 1/10 of the voltage at base frequency
■ Torque boost
• Manual torque boost by F09 (Manual adjustment)
• Data setting range: 0.0 to 20.0 (%), (100%/base frequency voltage)
In torque boost using F09, constant voltage is added to the basic V/f pattern, regardless of the load. To secure a
sufficient starting torque, manually adjust the output voltage to optimally match the motor and its load by using F09.
Specify an appropriate level that guarantees smooth Startup and yet does not cause over-excitation at no or light
load.
Torque boost using F09 ensures high driving stability since the output voltage remains constant regardless of the
load fluctuation.
Specify the function code F09 data in percentage to the base frequency voltage. At factory shipment, boost amount
with which approx. 100% of starting torque can be assured, is specified.