9.2.10 Inverter operation in CANopen communication
This chapter describes the inverter’s operation by using the CANopen communication.
There are the following two ways to run the inverter:
1. Operation according to CANopen’s drive profile (DSP 402)
2. Operation according to the inverter function code S06
[ 1 ] Operation according to CANopen’s drive profile (DSP 402)
(1) Related object list
Index
(Hex)
Sub Name Description Data type Access
6040 - Controlword Controls the state change of state machine UNSIGNED16 RW
6041 - Statusword Displays the current state. UNSIGNED16 R
6042 - vl target velocity Speed command (r/min) INTEGER16 RW
6044 - vl control effort Monitor the output speed (r/min) INTEGER16 R
604B - vl set-point factor
Modifies the resolution and specified range of
the speed settings.
ARRAY RW
As for the inverter’s operation, PDO No.2 is useful which can send both Controlword and speed
command at the same time.
X4 X3 X2 X1 Reverse 0 0 Halt
bits 0 to 3 : Operates the state change of state machine. Refer to Figure 9.2-3.
bit 7 Fault reset : Resets the alarm by change from zero to one.
bit 8 Halt : 1= Fixes the inverter’s output speed at 0 r/min.
bit 11 Reverse : Sets the rotation direction. 0= rotates forward, 1=rotates backward
bits 12 to 15 : Digital input terminal X1 to X4. 0=OFF, 1=ON