10.4 Selecting an Inverter Drive Mode (ND/HD/HND/HHD)
10-16
10.4.2 Guideline for selecting inverter drive mode and capacity
Table 10.4-1 lists the functional differences between ND, HD, HND, and HHD modes.
If the ND mode does not satisfy the requirements in your application in view of the overload capability and
functionality, you need to select the inverter one or two ranks higher in capacity (HD/HND/HHD mode) than that of
the motor rating.
To use the inverter under the ambient temperature or carrier frequency condition changed from the factory default,
the output current rating requires derating due to the ambient temperature or carrier frequency. It is, therefore,
necessary to select the inverter unit, referring to Figure 10.4-1 through Figure 10.4-4.
Table 10.4-1 Functional Differences between ND, HD, HND, and HHD Modes
Function ND mode HD mode HND mode HHD mode
Application General load Heavy duty load General load Heavy duty load
Data for function
code F80
“4”
(Factory default) *4
“3” “1” “0”
Continuous current
rating level (inverter
rated current level)
100% (Operating temperature: 40°C (104°F))
80% (Operating temperature: 50°C (122°F))
(See Figure 10.4-1.)
100% (Operating temperature: 50°C(122°F))
Overload capability
120% for 1 min. 150% 1 min. 120% 1 min.
150% for 1 min.
200% for 0.5 s
Maximum frequency
*1
Setting range:
25 to 120 Hz
Upper limit: 120Hz
Setting range: 25 to 500 Hz
Upper limit: 500 Hz
DC braking
(Braking level)
*1
Setting range:
0 to 60%
(Based on the rated
current level of
ND-mode inverter)
Setting range:
0 to 80%
(Based on the rated
current level of
HD-mode inverter)
Setting range:
0 to 80%
(Based on the rated
current level of
HND-mode inverter)
Setting range:
0 to 100%
(Based on the rated
current level of
HHD-mode inverter)
Motor sound
(Carrier frequency)
*1
Setting range:
0.75 to 10 kHz
(FRN0002E2■-4 to
FRN0059E2■-4)
(FRN0012E2■-2,
FRN0020E2■-2)
0.75 to 6 kHz
(FRN0072E2■-4 to
FRN590E2■-4)
Setting range:
0.75 to 16 kHz
(FRN0001E2-2 to FRN0088E2-2)
(FRN0002E2-4 to FRN0059E2■-4)
0.75 to 10 kHz
(FRN0072E2■-4 to FRN0168E2■-4)
(FRN0115E2■-2)
0.75 to 6 kHz
(FRN0203E2■-4 to FRN0590E2■-4)
Setting range:
0.75 to 16 kHz
(FRN0001E2■-2 to
FRN0115E2■-2)
(FRN0002E2■-4 to
FRN0168E2■-4)
(FRN0001E2-7 to
FRN0011E2■-7)
0.75 to 10 kHz
(FRN0203E2■-4 to
FRN0590E2■-4)
Current limiter (Level)
*2
Initial value: 130% Initial value: 160% Initial value: 130%
Initial value:
160% or 180% *3
Current indication
and output
Based on the rated
current level of
ND-mode inverter
Based on the rated
current level of
HD-mode inverter
Based on the rated
current level of
HND-mode inverter
Based on the rated
current level of
HHD-mode inverter
Note: A box () in the above table replaces S: Standard or E: EMC filter built-in type.
A box () in the above table replaces GA, GB or C depending on the model.
*1 In the ND/HD/HND mode, a setting value out of the range will be replaced with the upper limit of each mode.
*2 Mode switching with function code F80 initializes the current limiter level.
*3 FRN0011E2■-7 / FRN0069E2■-2 / FRN0044E2■-4 or below is 180%, FRN0088E2■-2 /
FRN0059E2■-4 or above is 160%.
*4 FRN0011E2■-7 or below is 0(HHD), FRN0010E2■-2 or below is 1(HND)”.
FRN0030E2■-2 or above is 1(HND),