LED monitor
shows:
(item No.):
Item Description
6_16
Multiple alarm 1
Simultaneously occurring alarm code (1)
(“
----
” is displayed if no alarm has occurred.)
6_17
Multiple alarm 2
Simultaneously occurring alarm code (2)
(“
----
” is displayed if no alarm has occurred.)
6_18
Terminal I/O signal status under
communications control
(displayed with the ON/OFF of
LED segments)
Shows the ON/OFF state of the digital I/O terminals under
RS-485 communications control when alarm occurred. Refer to
“ Displaying control I/O signal terminals under communications
control” in “3.4.4 Checking I/O signal status “I/O Checking:
$i_o
”” for details.
6_19
Terminal input signal status
under communications control
(in hexadecimal)
6_20
Terminal output signal status
under communications control
(in hexadecimal)
6_21
Error sub code Secondary error code for an alarm.
6_22
Running status 2
Running status 2 when alarm occurred as four hexadecimal
digits.
For details, refer to “Table 3.4-5 Running Status 2 (
3_23
) Bit
Assignment” in “3.4.3 Monitoring the running status “Drive
Monitoring:
#ope
”.”
6_23
Detected speed Shows the detected speed value when alarm occurred.
6_24
Running status 3
Running status 3 when alarm occurred as four hexadecimal
digits.
For details, refer to “Table 3.4-14 Running Status 3 (
3_24
) Bit
Assignment” given below.
6_25
Multiple alarm sub code Secondary error code for a multiple alarm.
Content
15 ― Always “0.” 7 FAN “1” when the fan is in operation.
14 ID2 “1” when current 2 is detected. 6 KP “1” during keypad operation.
13 IDL “1” when low current is detected. 5 OL
“1” when a motor overload early
warning is issued.
12 ID “1” when current is detected. 4 IPF
“1” during auto-restarting after
momentary power failure.
11 OLP “1” under overload prevention control. 3 SWM2 “1” when motor 2 is selected.
10 LIFE
“1” when a lifetime early warning is
issued.
2 RDY “1” when the inverter is ready to run.
9 OH
“1” when a heat sink overheat early
warning is issued.
1 FDT “1” when frequency is detected.
8 TRY “1” during auto-resetting. 0 FAR
“1” when a frequency arrival signal is
issued.