Basic key operation
This section gives a description of the basic key operation in “Quick Setup,” following the example of the function
code data changing procedure shown in Figure 3.4-6.
This example shows you how to change function code F01 data (Frequency setting 1) from the factory default “ /
keys on keypad (F01 = 0)” to “Current input to terminal [C1] (C1 function) (4 to 20 mA DC) (F01 = 2).”
(1) Turn the inverter ON. It automatically enters Running mode in which you press the
key to switch to
Programming mode. The function selection menu appears. (In this example,
*fnc
is displayed.)
(2) If anything other than
*fnc
is displayed, use the and keys to display
*fnc
.
(3) Press the key to proceed to the list of function codes.
(4) Use the and keys to display the desired function code (
f 01
in this example), then press the key.
The data of this function code appears. In this example, data
0
of
f 01
appears.
(5) Change the function code data using the and keys. In this example, press the key two times to
change data
0
to
2
.
(6) Press the key to establish the function code data.
The
saue
appears (blinking) and the data will be saved in the memory inside the inverter. After that, the
display will return to the function code list and then move to the next function code. In this example,
f 02
.
Pressing the key instead of the key cancels the change made to the data. The data reverts to the
previous value, the display returns to the function code list, and the original function code reappears.
(7) Press the key to return to the menu from the function code list.