(2) Tuning under vector control for PMSM without speed sensor and magnetic pole position sensor
■ Selection of PMSM type and pole position detection method
After identifying the type of the synchronous motor and selecting the magnetic pole position detection mode,
execute tuning based on Figure 4.8-3.
Tuning errors might occur during tuning depending on the type of the synchronous motor and mismatching
of P30 setting. Consult with the motor maker for the type and set the type to P30.
known, execute
tuning as P30=0. In this case, it might be necessary to adjust the starting frequency setting F23 or starting
frequency continuous time F24.
IPM type?
START
Yes
No
Er7
Yes
No
Yes
SPM type ?
Yes
No
Yes
No
(Unknown type)
Tune with P30 = 1
(Factory default)
Tune after changing P30 = 2
Er7
Tune after changing P30 = 0
(Only rotation Tuning is available)
Tune after changing P30 = 3
(Only rotation Tuning is available)
END
Set
- Starting frequency F23
- Starting frequency (Holding time) F24.
Aim value:
F23 = 1. 0 Hz, F24 = 1.0 s
Consult Fuji Electric.
(Report the error subcode value.)
No
Yes
Er7
Refer to Chapter 3 for the displaying method of error
subcode (6_21).
Refer to “Tuning errors (For PMSM)” for details.
Set
- Starting frequency F23
- Starting frequency (Holding time) F24.
Aim value:
F23 = 1. 0 Hz, F24 = 1.0 s