5.3 Description of Function Codes
5-46
F01
Frequency setting 1
Related function codes:
F18 bias (for frequency setting 1)
C30 frequency setting 2
C31 to C35 analog input adjustment (Terminal [12])
C36 to C39 analog input adjustment (Terminal [C1] (C1 function))
C40 terminal [C1] (C1 function) (Range / polarity selection)
C41 to C45 analog input adjustment (Terminal [C1] (V2 function))
C55 to C56 analog input adjustment (Terminal [12]) (Bias
Bias base point)
C61 to C62 analog input adjustment (Terminal [C1] (C1 function)
(Bias
Bias base point)
C67 to C68 analog input adjustment (Terminal [C1] (V2 function))
(Bias
Bias base point)
C50 bias (for frequency setting 1) (Bias base point)
H61 UP/DOWN control initial value selection
d59, d61 to d63 Command (Pulse train input)
Select setting method of frequency setting. Set frequency setting 1 by function code F01, frequency setting 2 by
C30.
F01, C30 data Command sources
0 Frequency setting by keypad (refer to the following descriptions to find the setting method)
1
Set by voltage value to be input in the terminal [12] (0 to ±10VDC, Maximum output frequency
/DC±10V)
2
Setting by current value to be input in the terminal [C1] (C1 function) (4 to 20mADC or 0 to 20
mADC, Maximum output frequency / 20 mADC)
(Set slide switch SW4 of printed circuit board to [AI] side (factory default state), SW3 to [C1]
side (factory default state), respectively.)
(It is necessary to select C1 function (factory default state) by E59=0)
(It is necessary to disable PTC input function by H26=0)
3
Set by the addition result of voltage value to be input in the terminal [12] (0 to ±10VDC,
Maximum output frequency /±10 VDC) and current value to be input in the terminal [C1] (C1
function) (4 to 20 mA DC or 0 to 20 mA DC, Maximum output frequency/20 mA DC)
When the addition result becomes maximum output frequency or higher, it is restricted by the
maximum output frequency)
5
Set by voltage value to be input in the terminal [C1] (V2 function) (0 to +10 VDC, Maximum
output frequency /+10 VDC)
(Set slide switch SW4 of printed circuit board to [AI] side (factory default state), SW3 to [V2]
side, respectively.)
(It is necessary to select V2 function by E59 = 1)
(It is necessary to disable PTC input function by H26 = 0)
7
Set by UP command UPand DOWN command DOWNassigned to the digital input terminal
It is necessary to assign UP command (Data = 17) and DOWN command (Data =18) to the
digital input terminal [X1] to [X5]. (E01 toE05)
8 Frequency setting by keypad (with balanceless bumpless function)
10 Set by pattern operation (C21 to C28)
11
Enable a digital input/output interface card (option).
(For details, refer to the Digital Input Output Interface Card Instruction Manual.)
12
Setting by pulse train input “PIN” (Data = 48), which was assigned to the digital input terminal
[X5], or the optional PG interface card.
Note: When using X5 terminal with pulse train input, it might be affected by noise from other
wire. Keep away from other wire from the wire to X5 terminal as far as possible.