Base frequency 1, Rated voltage at base frequency 1 
Maximum output voltage 1 
Related function codes:  H50, H51 Non-linear V/f 1 (Frequency, voltage) 
H52, H53 Non-linear V/f 2 (Frequency, voltage) 
H65, H66 Non-linear V/f 3 (Frequency, voltage) 
 
Set the base frequency and base frequency voltage that are essential to operation of the motor. By combining 
related function codes H50 to H53, H65, and H66, it is possible to set non-linear V/f pattern (weak or strong voltage 
by arbitrary point) and perform setting of V/f characteristics that is suitable for the load.   
Impedance of the motor becomes larger with high frequency, and when output voltage becomes less, output 
torque may be reduced. In order to prevent this, increase the voltage at high frequency by setting function code 
F06 (maximum output voltage 1). However, it is not possible to output voltage at or higher than the input power 
voltage of the inverter. 
Point of V/f 
Function code 
Remarks 
Frequency  Voltage 
Maximum output 
frequency 
F03  F06 
During auto torque boost, vector control with/ without speed 
sensor, the maximum output voltage setting is disabled. 
Base frequency  F04  F05   
Non-linear V/f 3  H65  H66 
This code is disabled during auto torque boost, vector control 
with/ without speed sensor. 
Non-linear V/f 2  H52  H53 
Non-linear V/f 1  H50  H51 
 
<Setting example> 
■  Normal V/f pattern setting 
 
 
■  Non-linear V/f pattern setting (3 points) 
 
 
Output voltage (V)