DC braking1 (Starting frequency, braking level, braking time)
DC braking (Braking response mode)
DC braking (Braking timer at the startup)
These function codes specify the DC braking that prevents motor 1 from running by inertia during
decelerate-to-stop operation.
If the motor enters a decelerate-to-stop operation by turning OFF the run command or by decreasing the reference
frequency below the stop frequency, the DC braking starts when output frequency reached the DC braking starting
frequency. Set braking starting frequency (F20), braking level (F21), and braking time (F22) to start DC braking
when deceleration is stopped.
Setting the braking time to “0.00” (F22 = 0) disables the DC braking.
By H195, it is possible to perform DC braking when starting up inverter. By doing so, it is efficient for preventing
from falling down when the brake is released, and prompt torque startup when starting up.
■ Braking starting frequency (F20)
F20 specifies the frequency at which the DC braking starts its operation during motor decelerate-to-stop state.
• Data setting range: 0.0 to 60.0 (Hz)
■ Braking level (F21)
F21 specifies the output current level to be applied when the DC braking is activated. The function code data
should be set, assuming the rated output current of the inverter as 100%, in increments of 1%.
• ND:0 to 60(%), HD/HND:0 to 80%,HHD:0 to 100%