5.3 Description of Function Codes
5-95
FUNCTION CODES
Chap 5
Control parameters which are initialized when the control method F42 is changed
When control method (F42) is switched between synchronous motor and induction motor, the data of related
function codes are also switched to the default value. See the table below.
Function code
Switch F42 between
15 and others
Change
P02
H03=2 with
F42=0 to 4,6
H03=2 with
F42=15
F03 Y N N N
F04 Y N N Y
F05 Y N N Y
F06 Y N N Y
F10 N N N Y
F11 Y N N Y
F12 Y N N Y
F15 Y N N N
F23 Y N N N
F26 Y N N N
F40 to F41 Y N N N
E50 Y N N N
P01 Y N Y Y
P02 N N N N
P03 Y Y Y Y
P05 to P13 N Y Y Y
P16-P20 N Y Y Y
P30 N Y Y Y
P53 N Y Y Y
P55 to P56 N Y Y Y
P60 to P64 N Y Y Y
P65 N Y Y Y
P74 N Y Y Y
P83 N Y Y Y
P84 N Y Y Y
P85 N Y Y Y
P87 to P89 N Y Y Y
P90 N Y Y Y
P99 Y N N N
H46 N Y Y Y
d01 to d04 Y N N N
Y: Switched N: Not switched