5.3 Description of Function Codes
5-147
FUNCTION CODES
Chap 5
C58
C64
C70
Analog input adjustment (for analog monitor (terminal [12])) (Display unit)
Analog input adjustment (for analog monitor (terminal [C1])) (C1 function) (Display unit)
Analog input adjustment (for analog monitor (terminal [C1])) (V2 function) (Display unit)
The units for the respective analog inputs can be displayed when a multi-function keypad (TP-A1-E2C) is used. Set
these codes to use for command and feedback values of the PID control and the analog input monitor. Use the
multi-function keypad to display the SV and PV values of the PID control and the analog input monitor on the main
and sub-monitors. Indications are given in the specified units.
C58, C64,
C70
Unit C58, C64, C70
Unit
— — 23 L/s (flowrate) 45 mmHg (pressure)
1 No unit 24 L/min (flowrate) 46 Psi (pressure)
2 % 25 L/h (flowrate) 47 mWG (pressure)
4 r/min 40 Pa (pressure) 48 inWG (pressure)
7 kW 41 kPa (pressure) 60 K (temperature)
20 m
3
/s (flowrate) 42 MPa (pressure) 61 °C (temperature)
21 m
3
/min (flowrate) 43 mbar (pressure) 62 °F (temperature)
22 m
3
/h (flowrate) 44 bar (pressure) 80 ppm (concentration)
C59, C60
C65, C66
C71, C72
Analog input adjustment (terminal [12]) (Maximum scale, Minimum scale)
Analog input adjustment (terminal [C1] (C1 function)) (Maximum scale, Minimum scale)
Analog input adjustment (terminal [C1] (V2 function)) (Maximum scale, Minimum scale)
Values of the analog input monitor (terminals [12] and [C1] (C1 and V2 functions) can be converted into easily
recognizable physical quantities for display. This function can also be used for PID feedback and PID command
values.
• Data setting range: (maximum scale and minimum scale) -999.00 to 0.00 to 9990.00
Analog input
(terminal [12])