User initial value (save, protection)
Relevant function code: Initialization of H02 and H03 data
(initial value selection and target)
The value can be saved in the non-volatile memory in the inverter so that customers may use the setting value
changed from the Fuji Electric standard factory default value as the initial value for inverter initialization.
The setting value saved and protected here can be selected as the user initial value for initialization with function
code H03. When this function is used, set H02 data=1.
If initialization is performed without saved/protected setting data, it is initialized to the Fuji Electric standard factory
default regardless of the H02 value.
For data initialization, refer to function codes H02 and H03.
To change the data of function codes H02,H193 and H194, it is necessary to operate double keys “ key + /
key”.
To save the user setting value, set 1 (saved as the user initial value) to function code H02 in advance. In addition,
function code H194 must be set to 0 (save enable).
H02 data H194 data Function when 1 is set to H193
0 Optional User setting value is not saved.
1 0:Save enable User setting value is saved.
1:Protected (save disable) User setting value is not saved.
User initial value save procedures
(1) Set all function codes and determine the user setting value for initialization.
(2) Set H02=1 and H194=0.
(3) Set H193=1. The user setting value is saved.
(4) Set H194=1. The user setting value is protected.
When the setting value of the function code has already saved by H193 and the step of H193 is repeated
again, the saved data is overwritten. Be careful for error operation. To prevent overwriting by error, it is
recommended to protect the data with