5.3 Description of Function Codes
5-194
Table 5.3-19 Function Codes to be Switched (contd)
Name
Function code
1st motor 2nd motor
(Iron loss factor 1) P13 A27
(Magnetic saturation factor 1 to 5) P16 to P20 A30 to A34
(%X correction factor 1) P53 A53
(Torque current under vector control) P55 A55
(induced voltage factor under vector control) P56 A56
Speed control (Speed command filter) d01 A43
(Speed detection filter) d02 A44
(P Gain) d03 A45
(Integral time) d04 A46
(FF Gain) d05 A47
(Notch filter resonance frequency) d07 A49
(Notch filter attenuation level) d08 A50
Motor selection P99 A39
Slip compensation (Operating conditions) H68 A40
Output current fluctuation damping gain for motor H80 A41
Cumulative motor run time H94 A51
Startup count for motor H44 A52
Reserved for particular manufacturers d51 d52
Table 5.3-20 Function Codes not available for the Motor 2
Data Function codes 2nd motor operation
Non-linear V/f pattern H50 to H53, H65, H66 Disabled
Starting frequency 1 (Holding time) F24 Disabled
Stop frequency (Holding time) F39 Disabled
Motor overload early warning E34, E35 Disabled
Droop control H28 Disabled
UP/DOWN control H61 Fixed at the initial setting (0 Hz)
PID control J01 to J06, J08 to J13, J15 to J19
J56 to J62, J105 to J138, H91
Disabled
Brake signal J68 to J72, J95, J96 Disabled
Current limiter F43, F44 Disabled
Rotational direction limitation H08 Disabled
Maintenance Interval/ Preset startup
count for maintenance
H78, H79 Disabled
DC braking
(Braking timer at the startup)
H195 Disabled
PMSM drive F42 Disabled