5.3 Description of Function Codes
5-264
[Input: digital, analog] Block function code setting
Lock selection, function 1, function 2 (U01, U04, U05, etc.) (digital,analog)
The following items are available as function block.
Note that if the upper and lower limits are identical, there are no upper and lower limits.
Block
selection
(U01 etc.)
Function block Description
Function 1
(U04 etc.)
Function 2
(U05 etc.)
4001 Hold Function to hold analog input 1 based on digital input
1.
Upper limit Lower limit
4002 Inverting adder
with enable
Function to reverse analog input 1 based on digital
input 1.
Subtracted
value
(former)
Addition value
(latter)
4003 Selector 1 Function to select analog input 1 and setting value
based on digital input 1.
Setting
value
Not
required
4004 Selector 2 Function to select setting value 1/2 based on digital
input 1.
Setting
value 1
Setting
value 2
4005 LPF
(Low pass filter)
with enable
Value of an analog input 1 is filtered through LPF
(time constant U04) when the digital input 1 is “1”.
When the digital input 1 is “0”, the analog input 1 is
directly output.
(LPF maintains the previous output value. Therefore,
when the digital 1 input changes from 0 to 1, the
output will be the value with the previous output value
added as the initial value of LPF.)
(No upper/lower limiter)
Time
constant
0: No filter
0.01 to 5.00s
Fixed as 0
4006 Rate limiter with
enable
Value of an analog input is limited with change rate
specified in functions 1 and 2 when the digital input 1
is “1”. When the digital input 1 is “0”, the analog 1
input is directly output. When setting the initial value,
carry out an operation with the initial value for input 1
and 0 applied to input 2. Then, reflect the result as the
initial value (= previous output value) with 1 applied to
input 2.
During the initialization or when the CLC terminal is
ON, the previous output value is cleared to 0.
Upward
change rate
Time taken
to change
100%
0: No limit
0.01 to 600 s
Downward
change rate
Time
taken to
change
100%
0: The same
change rate
as function 1
0.01 to 600 s
5000 Selector 3 Function to select analog input 2 based on SO01to
SO200”.
Step No. Not required
5100 Selector 4 Function to select analog input 1 and SO01to
SO200based on digital input 1.
Step No. Not required
6001 Reading
function codes
Function to read the content of arbitrary function
code. Use the 1st function code (such as U04) to
specify a function code group, and the 2nd one (such
as U05) to specify the last two digits of the function
code number. For the function code settings, refer to
Configuration of function codesin page 5-270.
Both input 1 and input 2 are not used. Data formats
that can be read correctly are as follows (the values
are restricted between -9990 and 9990 and, for [29],
20000 is indicated as 100%):
[1], [2], [3], [4], [5], [6], [7], [8], [9], [10], [12], [22], [24],
[29], [35], [37], [45], [61], [67], [68], [74], [92] and [93]
Data formats other than the above cannot be read
correctly. Do not use any other format.