FUNCTION CODES
Chap 5
■ Output signal (Digital,analog)
In the customizable logic, outputs from steps 1 to 10 are issued to SO01 to SO200, respectively.
SO01 to SO200 differ in configuration depending upon the connection destination, as listed below. To relay those
outputs to any function other than the customizable logic, route them via customizable logic outputs CL01 to
CLO010.
Connection destination of each
step output
Configuration Function code
Input of customizable logic Select one of the internal step output signals “SO01” to
“SO200” in customizable logic input setting.
Such as U02
and U03
Input of inverter sequence
processor
(such as multistep speed “SS1”
or operation command “FWD”)
Select one of the internal step output signals “SO01” to
“SO200” to be connected to customizable logic output
signals 1 to 10 (“CL01” to “CLO10”).
U71 to U80
Select an inverter’s sequence processor input function to
which one of the customizable logic output signals 1 to 10
(“CL01” to “CLO10”) is to be connected. (Same as in E01)
U81 to U90
Analog input
(such as auxiliary frequency
commands or PID process
commands)
Select one of the internal step output signals “SO01” to
“SO200” to be connected to customizable logic output
signals 1 to 10 (“CL01” to “CLO10”).
U71 to U80
Select an analog input function to which one of the
customizable logic output signals 1 to 10 (“CL01” to
“CLO10”) is to be connected. (Same as in E61)
U81 to U90
General-purpose digital output
([Y] terminals)
Select one of the internal step output signals “SO01” to
“SO200” to be connected to customizable logic output
signals 1 to 10 (“CL01” to “CLO10”).
U71 to U80
To specify a general-purpose digital output function (on [Y]
terminals) to which one of the customizable logic output
signals 1 to 10 (“CL01” to “CLO10”) is to be connected,
select one of “CLO1” to “CLO10” by specifying the
general-purpose digital output function on any Y terminal.
E20, E21,
E27
General-purpose analog output
([FM] terminals)
Select one of the internal step output signals “SO01” to
“SO200” to be connected to customizable logic output
signals 1 to 10 (“CL01” to “CLO10”).
U71 to U80
To specify a general-purpose analog output function (on
[FM] terminals) to which one of the customizable logic
output signals 1 to 10 (“CL01” to “CLO10”) is to be
connected, select one of “CLO1” to “CLO10” by specifying
the general-purpose digital output function on any [FM]
terminal.
F31, F35