) 
are Displayed 
This section describes the troubleshooting procedure based on function codes dedicated to motor 1. When motor 2 
is used, it is necessary to convert to the corresponding function codes. The function codes that need to be 
converted are marked with “*.” 
  For the function codes to be converted, see Chapter 5 “FUNCTION CODES.” 
 
 
6.5.1    Abnormal motor operation 
[ 1 ]    The motor does not rotate 
Possible Causes  Check and Measures 
(1)  No power supplied to the 
inverter. 
Check the input voltage and interphase voltage unbalance. 
  Switch on the molded-case circuit breaker, an earth-leakage circuit 
breaker (with overcurrent protective function) or a magnetic 
contactor. 
  Check for voltage drop, phase loss, poor connections, or poor 
contacts, and fix them if necessary. 
  If only the auxiliary control power input is supplied, also supply the 
main power to the inverter. 
(2)  No forward/reverse operation 
command was inputted, or both 
the commands were inputted 
simultaneously (external signal 
operation). 
Check the input status of the forward/reverse command with Menu “I/O 
Checking” using the keypad. 
  Input a run command. 
  Set either the forward or reverse operation command to OFF. 
  Correct the run command source. Set F02 data to “1.” 
  Correct the assignment error of terminals [FWD], [REV]. (E98, E99) 
  Connect the external circuit wires to control circuit terminals [FWD] 
and [REV] correctly. 
  Make sure that the sink/source slide switch (SW1) on the control 
printed circuit board (control PCB) is properly configured. 
(3)  No rotational direction is 
instructed. 
(Keypad operation) 
Check the input status of the forward/reverse rotation direction 
command with Menu “I/O Checking” using the keypad. 
  Input the rotation direction (F02 = 0), or select the keypad operation 
with which the rotation direction is fixed (F02 = 2 or 3). 
(4)  The inverter could not accept 
any run commands from the 
keypad since it was in 
Programming mode. 
Check which operation mode the inverter is in, using the keypad. 
  Shift the operation mode to Running mode and enter a run 
command. 
(5)  A run command with higher 
priority than the one attempted 
was active, and the run 
command was stopped. 
Based on the run command block diagram (See Chapter 8 “BLOCK 
DIAGRAMS FOR CONTROL LOGIC”), check a higher priority run 
command by function code data check and I/O checking from Menu 
using the keypad. 
  Correct any incorrect function code data settings such as link 
function (Mode selection) (H30) and bus link function (Mode 
selection) (y98) or cancel the higher priority run command. 
(6)  No analog frequency command 
input. 
Check that a reference frequency has been entered correctly, using 
Menu “I/O Checking” on the keypad. 
  Connect external circuit wirings of terminals [13], [12], [11], [C1] 
correctly.