11.3 Molded Case Circuit Breaker (MCCB), Residual-current-operated Protective Device
(RCD)/Earth Leakage Circuit Breaker (ELCB) and Magnetic Contactor (MC)
11-13
SELECTING PERIPHERAL EQUIPMENT
Chap 11
Table 11.3-1 Rated Current of Molded Case Circuit Breaker (MCCB), Residual-Current-Operated Protective
Device (RCD)/ Earth Leakage Circuit Breaker (ELCB) and Magnetic Contactor (MC) (continued)
ND, HD, HND, HHD mode (HP rating motor)
Voltage
class
Nominal
applied
motor
(HP)
Inverter type
ND mode
Inverter type
HD mode
Inverter type
HND mode
Inverter type
HHD mode
MCCB, RCD/ELCB
rated current (A)
Magnetic contactor (MC)
Input circuit
Output
circuit
DC reactors (DCRs)
DC reactors (DCRs)
w/ DCR
w/o DCR
w/ DCR
w/o DCR
Three-pahse 230V class
1/8
-
-
-
FRN0001E2-2
5
5
SC-05
SC-05
SC-05
1/4
-
-
FRN0001E2-2
FRN0002E2-2
1/2
-
-
FRN0002E2-2
FRN0004E2-2
1
-
-
FRN0004E2-2
FRN0006E2-2
10
1.5
-
-
FRN0006E2-2
-
10
2
-
-
-
FRN0010E2-2
15
3
-
-
FRN0010E2-2
FRN0012E2-2
20
4
-
-
FRN0012E2-2
-
20 30
5
-
-
-
FRN0020E2-2
SC-4-0
7.5 - -
FRN0020E2-2
-
30
40
SC-4-0 SC-5-1 SC-4-0
-
FRN0030E2-2
50
10
-
-
FRN0030E2-2
FRN0040E2-2
40
75
SC-5-1
SC-N1
SC-N1
15
-
-
FRN0040E2-2
FRN0056E2-2
50
100
SC-N1
SC-N2S
20
-
-
FRN0056E2-2
FRN0069E2-2
75
125
SC-N2
SC-N3
SC-N2
25
-
-
FRN0069E2-2
FRN0088E2-2
100
150
SC-N2S
SC-N4
SC-N2S
30
-
-
FRN0088E2-2
FRN0115E2-2
175
SC-N5
SC-N3
40
-
-
FRN0115E2-2
-
150
200
SC-N4
SC-N7
SC-N4
Three-pahse 460V class
1/2
-
-
-
FRN0002E2-4
5
5
SC-05
SC-05
SC-05
1
FRN0002E2-4
FRN0002E2-4
FRN0002E2-4
FRN0004E2-4
1.5
-
FRN0004E2-4
FRN0004E2-4
-
2
FRN0004E2-4
-
-
FRN0006E2-4
10
3
FRN0006E2-4
FRN0006E2-4
FRN0006E2-4
FRN0007E2-4
10
15
4
FRN0007E2-4
FRN0007E2-4
FRN0007E2-4
-
5
-
-
-
FRN0012E2-4
20
7.5
FRN0012E2-4
FRN0012E2-4
FRN0012E2-4
FRN0022E2-4
15
30
10
-
FRN0022E2-4
FRN0022E2-4
FRN0029E2-4
20
40
SC-4-0
15
FRN0022E2-4
FRN0029E2-4
FRN0029E2-4
FRN0037E2-4
30
50
SC-4-0
SC-N1
SC-4-0
20
FRN0029E2-4
FRN0037E2-4
FRN0037E2-4
FRN0044E2-4
40
60
SC-5-1
SC-5-1
25
FRN0037E2-4
FRN0044E2-4
FRN0044E2-4
FRN0059E2-4
75
SC-N1
SC-N2
SC-N1
30
FRN0044E2-4
FRN0059E2-4
FRN0059E2-4
FRN0072E2-4
50
100
SC-N2S
40
FRN0059E2-4
FRN0072E2-4
FRN0072E2-4
FRN0085E2-4
75
125
SC-N2
SC-N3
SC-N2
50
FRN0072E2-4
FRN0085E2-4
FRN0085E2-4
FRN0105E2-4
100
SC-N2S
SC-N4
SC-N2S
60
FRN0085E2-4
FRN0105E2-4
FRN0105E2-4
FRN0139E2-4
150
SC-N3
SC-N3
75
FRN0105E2-4
FRN0139E2-4
FRN0139E2-4
FRN0168E2-4
125
200
SC-N5
SC-N4
100
FRN0139E2-4
FRN0168E2-4
FRN0168E2-4
FRN0203E2-4
175
-
SC-N4
-
SC-N5
125
FRN0168E2-4
FRN0203E2-4
FRN0203E2-4
FRN0240E2-4
200
SC-N7
SC-N7
150
FRN0203E2-4
FRN0240E2-4
FRN0240E2-4
FRN0290E2-4
250
SC-N8 SC-N8
200
FRN0240E2-4
FRN0290E2-4
FRN0290E2-4
FRN0361E2-4
300
250
-
FRN0361E2-4
FRN0361E2-4
FRN0415E2-4
350
SC-N11
SC-N11
300
FRN0361E2-4
FRN0415E2-4
FRN0415E2-4
FRN0520E2-4
500 SC-N12 SC-N12
350
FRN0415E2-4
FRN0520E2-4
FRN0520E2-4
FRN0590E2-4
400
-
FRN0590E2-4
-
-
600
SC-N14 SC-N14
450
FRN0520E2-4
-
FRN0590E2-4
-
800
500
FRN0590E2-4
-
-
-
SIngle-pahse
230V class
1/8
-
-
-
FRN0001E2-7
5
5
SC-05
SC-05
SC-05
1/4
-
-
-
FRN0002E2-7
1/2
-
-
-
FRN0003E2■-7
10
1
-
-
-
FRN0005E2■-7
10
15
2
-
-
-
FRN0008E2■-7
15
20
3
-
-
-
FRN0011E2■-7
20
30
SC-5-1
Note:A box (■) in the above table replaces S (Basic type) or E (EMC filter built-in type) depending on the enclosure.
A box () in the above table replaces GA, GB or C depending on the model.
Install the MCCB or RCD/ELCB at the input side of the inverter. They cannot be installed at the output side of
the inverter.
The above table lists the rated current of MCCBs and RCD/ELCBs to be used in the power control panel with an
internal temperature of lower than 50°C (122°F). The rated current is factored by a correction coefficient of 0.85
as the RCDs/MCCBs and ELCBs original rated current is specified when using them in a surrounding
temperature of 40°C (104°F) or lower. Select an MCCB and/or RCD/ELCB suitable for the actual short-circuit
breaking capacity needed for your power systems.
For the selection of the MC type, it is assumed that the 600 V HIV (allowable surrounding temperature: 75°C
(167°F)) wires for the power input/output of the inverter are used. If an MC type for another class of wires is
selected, the wire size suitable for the terminal size of both the inverter and the MC type should be taken into
account.
Use ELCBs with overcurrent protection.
To protect your power systems from secondary accidents caused by the broken inverter, use an MCCB and/or
RCD/ELCB with the rated current listed in the above table. Do not use an MCCB or RCD/ELCB with a rating
higher than that listed.