11.9 Power Regenerative PWM Converters, RHC Series
11-39
SELECTING PERIPHERAL EQUIPMENT
Chap 11
■ Required structure and environment
Required structure, environment and standards
Mounting in a panel or mounting for external cooling
Munsell 5Y3/0.5, eggshell
(Same color as our inverter FRENIC 5000VG7S series.)
Structure designed for easy parts replacement
Shall be free from corrosive gases, flammable gases, dusts, and
direct sunlight. Indoor use only.
5 to 95% RH (No condensation)
Altitude 3,000 m max. (For use in an altitude between 1,001 m to 3,000 m,
the output current should be derated.)
2 to 9 Hz: Amplitude = 3 mm, 9 to 20 Hz: 9.8 m/s
2
,
20 to 55 Hz: 2 m/s
2
(9 to 55 Hz: 2 m/s
2
for 90 kW or above),