Appendix G Conformity with Standards
Appendix-42
11. All models rated 380-480 V input voltage ratings shall be connected to TN-C system power source, i.e.
3-phase, 4-wire, wye (480Y/277V), so that the phase-to-ground rated system voltage is limited to 300V
maximum.
12
. Install UL certified fuses or circuit breaker between the power supply and the inverter, referring to the table
below.
Power supply voltage
Nominal applied motor(kW)[HP]
Inverter type
HHD/HD/HND/ND mode
Class J or Class CC
fuse size (A) *4
Circuit breaker trip size (A) *5
Required torque
lb-in (Nm)
Wire size AWG (mm
2
)
Main terminal
Inverter’s grounding
Aux. control power supply
Aux. Fan power supply
Main terminal Cu Wire
G
Aux. control power supply
Aux. fan power supply
L1/R,L2/S,L3/T U, V, W
60°C Cu wire
75°C Cu wire
Remarks
60°C Cu wire
75°C Cu wire
Remarks
Inverter’s
grounding
Three-phase 200V
0.1
[1/8]
FRN0001E2-2 HHD
3
5
7.1
(0.8)
10.6
(1.2)
14
(2.1)
14
(2.1)
14
(2.1)
0.2
[1/4]
FRN0001E2-2 HND
FRN0002E2-2 HHD
6
0.4
[1/2]
FRN0002E2
-2
HND
FRN0004E2-2 HHD
10
0.75
[1]
FRN0004E2
-2
HND
10
FRN0006E2-2 HHD
15
1.1
[1.5]
FRN0006E2-2 HND
1.5
[2]
FRN0010E2-2 HHD
20
10.6
(1.2)
15.9
(1.8)
12
(3.3)
2.2
[3]
FRN0010E2-2 HND
10
(5.3)
FRN0012E2
-2
HHD
30
3.0
[4]
FRN0012E2-2 ND
12
(3.3)
3.7
[5]
FRN0020E2-2 HHD 40
10
(5.3)
12
(3.3)
5.5
[7.5]
FRN0020E2
-2
ND
50
8
(8.4)
8
(8.4)
FRN0030E2S-2 HHD 60
27
(3.0)
27
(3.0)
10
(5.3)
7.5
[10]
FRN0030E2S-2
HND
75
FRN0040E2S-2 HHD
8
(8.4)
11
[15]
FRN0040E2S-2 HND
100
6
(13.3)
6
(13.3)
FRN0056E2S-2 HHD
51.3
(5.8)
51.3
(5.8)
15
[20]
FRN0056E2S-2
HND
150
4
(21.2)
6
(13.3)
FRN0069E2S-2 HHD
18.5
[25]
FRN0069E2S-2
HND
175
3
(26.7)
4
(21.2)
FRN0088E2-2 HHD 150
*3
14
(2.1)
*1
*2
22
[30]
FRN0088E2-2 HND
200 175
2
(33.6)
3
(26.7)
FRN0115E2-2 HHD
30
[40]
FRN0115E2-2 HND 250 200
2/0
(67.4)
2
(33.6)
3
(26.7)
5.5
[7.5]
FRN0030E2E-2 HHD 60
input
15.9
(1.8)
other
27
(3.0)
27
(3.0)
8
(8.4)
10
(5.3)
8
(8.4)
7.5
[10]
FRN0030E2E-2 HND
75
FRN0040E2E-2 HHD
8
(8.4)
11
[15]
FRN0040E2E-2
HND
100
6
(13.3)
6
(13.3)
FRN0056E2E-2 HHD
input
71.7
(8.1)
other
51.3
(5.8)
51.3
(5.8)
15
[20]
FRN0056E2E-2
HND
150
4
(21.2)
6
(13.3)
FRN0069E2E-2 HHD
18.5
[25]
FRN0069E2E-2 HND 175
3
(26.7)
4
(21.2)
Note: A box () in the above table replaces S (Basic type) or E (EMC filter built-in type) depending on the