Note: Control circuit terminals M2 tightening torque: 1.7 lb-in (0.19 N·m) ±10%
Recommended wire size: AWG26 to 18 (0.14 to 1 mm
2
)
M3 tightening torque: 4.4 to 5.3 lb-in (0.5 to 0.6 N·m), recommended wire size: AWG26 to 16 (0.14 to 1.5
mm
2
)
Note: A box (■) in the above table replaces S (Basic type) or E (EMC filter built-in type) depending on the
enclosure.
A box () in the above table replaces GA, GB or C depending on the model.
*1 No terminal end treatment is required for connection.
*2 Use 75°C (167°F) Cu wire only.
*3 The wire size of UL Open Type and Enclosed Type are common. Please contact us if UL Open Type
exclusive wire is necessary.
*4 6 rms Amperes for aux. control power supply. There is no aux. control power supply in FRN0020E2■
-2□ /FRN0022E2■-4/FRN0011E2■-7 or below.
*5 5 rms Amperes for aux. control power supply. There is no aux. control power supply in FRN0020E2■
-2□ /FRN0022E2■-4/FRN0011E2■-7 or below.