Appendix G Conformity with Standards
Appendix-44
Power supply voltage
Nominal applied motor(kW)[HP]
Inverter type
HHD/HD/HND/ND mode
Class J or Class CC
fuse size (A) *4
Circuit breaker trip size (A) *5
Required torque
lb-in (Nm)
Wire size AWG (mm
2
)
Main terminal
Inverter’s grounding
Aux. control power supply
Aux. Fan power supply
Main terminal Cu Wire
G
Aux. control power supply
Aux. fan power supply
L1/R,L2/S,L3/T U, V, W
60°C Cu wire
75°C Cu wire
Remarks
60°C Cu wire
75°C Cu wire
Remarks
Inverter’s
grounding
Three-phase 400V
5.5
[7.5]
FRN0022E2E-4 HHD 30
input
15.9
(1.8)
other
27
(3.0)
27
(3.0)
12
(3.3)
14
(2.1)
10
(5.3)
7.5
[10]
FRN0022E2E-4 HND
40
10
(5.3)
12
(3.3)
FRN0029E2E-4 HHD
11
[15]
FRN0029E2E-4 HND
60
8
(8.4)
10
(5.3)
8
(8.4)
FRN0037E2E-4 HHD
input
15.9
(1.8)
other
51.3
(5.8)
51.3
(5.8)
15
[20]
FRN0037E2E-4 HND
70
8
(8.4)
FRN0044E2E-4 HHD
10
(5.3)
18.5
[25]
FRN0044E2E-4 HND 90
6
(13.3)
6
(13.3)
Single-phase 200V
0.1
[1/8]
FRN0001E2-7
HHD 6 5
7.1
(0.8)
10.6
(1.2)
14
(2.1)
14
(2.1)
14
(2.1)
0.2
[1/4]
FRN0002E2-7
HHD 6 5
0.4
[1/2]
FRN0003E2-7
HHD 10 10
0.75
[1]
FRN0005E2-7
HHD 20 15
12
(3.3)
1.5
[2]
FRN0008E2-7
HHD 30
10.6
(1.2)
15.9
(1.8)
12
(3.3)
10
(5.3)
2.2
[3]
FRN0011E2-7
HHD 50
10
(5.3)
Note: Control circuit terminals M2 tightening torque: 1.7 lb-in (0.19 N·m) ±10%
Recommended wire size: AWG26 to 18 (0.14 to 1 mm
2
)
M3 tightening torque: 4.4 to 5.3 lb-in (0.5 to 0.6 N·m), recommended wire size: AWG26 to 16 (0.14 to 1.5
mm
2
)
Note: A box () in the above table replaces S (Basic type) or E (EMC filter built-in type) depending on the
enclosure.
A box () in the above table replaces GA, GB or C depending on the model.
*1 No terminal end treatment is required for connection.
*2 Use 75°C (167°F) Cu wire only.
*3 The wire size of UL Open Type and Enclosed Type are common. Please contact us if UL Open Type
exclusive wire is necessary.
*4 6 rms Amperes for aux. control power supply. There is no aux. control power supply in FRN0020E2
-2□ /FRN0022E2-4/FRN0011E2-7 or below.
*5 5 rms Amperes for aux. control power supply. There is no aux. control power supply in FRN0020E2
-2□ /FRN0022E2-4/FRN0011E2-7 or below.