Function
Prompt
Selections or
Range of Setting
Parameter Definition
Oxygen Oxygen Probe
Input
Input 1
Transmitter
TC B
TC E High
TC E Low
TC J High
TC J Mid
TC J Low
TC K High
TC K Mid
TC K Low
TC M High
TC M Low
TC N High
TC N Low
TC R
TC S
TC T High
TC T Low
TC W High
TC W Low
TC PR40-PR20
RTD Pt100
RTD Pt100 Low
RTD Pt200
RTD Pt500
Transmitter Characterization —This selection lets
you instruct the controller to characterize a
linear input to represent a non-linear one. If
characterization is performed by the transmitter
itself, then select Linear.
ATTENTION: Prompt only appears when a
linear actuation is selected at prompt
Input 1 Type.
FOR EXAMPLE:
If input 1 is a 4 to 20 mA signal, but the signal
represents a type K H thermocouple, then
configure K TC H and the controller will
characterize the 4 to 20 mA signal so that it is
treated as a type K thermocouple input (high
range).
Parameter definitions are the same as in Input 1
Type.
117
Chapter 4 - Configuration