EasyManua.ls Logo

Honeywell UDC2800 - Page 118

Honeywell UDC2800
432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
118
Function
Prompt
Selections or
Range of Setting
Parameter Definition
Linear
Square Root
Input 1 High
Value
–999. To 9999.
Floating (in
engineering
units)
Input 1 High Range Value in engineering units is
displayed for all inputs but can only be
configured for linear or square root transmitter
characterization.
Scale the #1 input signal to the display value you
want for 100 %.
FOR EXAMPLE:
Process Variable = Flow Range of Flow = 0 to 250
Liters/Minute Actuation (Input 1) = 4 to 20 mA
Characterization (XMITTER) = LINEAR Set IN1 HI
display value to 250 Set IN1 LO display value to
0 Then 20 mA = 250 Liters/Minute and 4 mA = 0
Liters/Minute
ATTENTION: The control setpoint will be
limited by the range of units selected here.
Input 1 Low
Value
–999. To 9999.
Floating (in
engineering
units)
Input 1 Low Range Value in engineering units is
displayed for all inputs but can only be
configured for linear or square root transmitter
characterization. Scale the #1 input signal to the
display value you want for 0 %. See example
above.
ATTENTION: The control setpoint will be
limited by the range of units selected here.
Input 1 Ratio –20.00 to 20.00
Floats to 3
decimal places
Ratio on Input 1 —Select the Ratio value you
want on Input 1.
Input 1 Bias –999. to 9999.
(in engineering
units)
Bias on Input 1 Bias is used to compensate
the input for drift of an input value due to
deterioration of a sensor, or some other cause.
Select the bias value you want on Input 1.
Chapter 4 - Configuration

Table of Contents

Other manuals for Honeywell UDC2800

Related product manuals