124
Function
Prompt
Selections or
Range of
Setting
Parameter Definition
RTD Pt100
Low
RTD Pt200
RTD Pt500
Linear
Square Root
Input 2 High
Value
–999. To
9999.
Floating (in
engineering
units)
Input 2 High Range Value in engineering units is
displayed for all inputs but can only be configured
for linear or square root transmitter
characterization.
See the example in Input 1 High.
Input 2 Low
Value
–999. To
9999. Floating
(in
engineering
units)
Input 2 Low Range Value in engineering units is
displayed for all inputs but can only be configured
for linear or square root transmitter
characterization.
See the example in Input 1 High.
Input 2 Ratio –20.00 to
20.00 Floats
to 3 decimal
places
Ratio on Input 2 —Select the Ratio value you want on
Input 2.
Input 2 Bias –999. to 9999.
(in
engineering
units)
Bias on Input 2 — Bias is used to compensate the
input for drift of an input value due to deterioration
of a sensor, or some other cause. Select the bias
value you want on Input 2.
Input 2 Filter 0 to 120
seconds No
filter = 0
Filter for Input 2 —A software digital filter is provided
for Input 1 to smooth the input signal. You can
configure the first order lag time constant from 1 to
120 seconds. If you do not want filtering, enter 0.
Input 2
Burnout
Burnout Protection (Sensor Break) provides most
input types with upscale or downscale protection if
the input fails.