130
Function
Prompt
Selections or Range
of Setting
Parameter Definition
ATTENTION: Only appears when PID
Sets is configured for 2 Sets PV
Switchover, 2 Sets SP Switchover, 4 Sets
PV Switchover, or 4 Sets SP Switchover.
Switchover
Value 2/3
Value in
engineering units
within PV or SP
range limits
Automatic Switchover Value- This is the value of
Process Variable or Setpoint at which the
controller will switch from Tuning Constant
Set #2 to Set #3.
ATTENTION: Only appears when PID
Sets is configured for 4 Sets PV
Switchover, or 4 Sets SP Switchover.
Switchover
Value 3/4
Value in
engineering units
within PV or SP
range limits
Automatic Switchover Value- This is the value of
Process Variable or Setpoint at which the
controller will switch from Tuning Constant
Set #3 to Set #4.
ATTENTION: Only appears when PID
Sets is configured for 4 Sets PV
Switchover, or 4 Sets SP Switchover.
Local SP
Source
Local Setpoint Source- This selection
determines how many local setpoints are
enabled.
1 Local SP The setpoint entered from the keyboard.
2 Local SP This selection lets you switch between two
local setpoints using the Function key under
the main screen.
3 Local SP This selection lets you switch between three
local setpoints using the Function key under
the main screen.
4 Local SP This selection lets you switch between four
local setpoints using the Function key under
the main screen.
Chapter 4 - Configuration