Function
Prompt
Selections or Range
of Setting
Parameter Definition
Remote SP
Source
Remote Setpoint Source—This selection
determines what your remote setpoint source
will be when toggled by the SP Select key or
Digital Input.
NONE No remote setpoint.
Input 2 Remote Setpoint is Input 2.
Input Algorithm 1 Remote Setpoint using Input 1 algorithm.
ATTENTION: To cycle through the
available local setpoints and remote
setpoint, press and hold in the Function
key. When the key is released, the
setpoint selection currently displayed
will be the new setpoint selection.
Autobias Autobias is used for bumpless transfer when
transferring from local setpoint to remote
setpoint. Auto Bias calculates and adds a bias
to remote setpoint input each time a transfer
is made.
Only available if no tracking is selected.
Disable Disables auto bias.
Enable Enables auto bias.
SP Tracking Setpoint Tracking- The local setpoint can be
configured to track either PV or RSP as listed
below. Not configurable when Auto Bias is set.
ATTENTION: For selections other than
NONE, LSP is stored in nonvolatile
memory only when there is a mode
change; i.e., when switching from RSP
to LSP or from Manual to Automatic. If
power is lost, then the current LSP
value is also lost.
None No Tracking- If local setpoint tracking is not
131
Chapter 4 - Configuration