Function Prompt
Selections or Range
of Setting
Parameter Definition
To Local SP 2 Contact closure puts the controller
into local setpoint 2.
To Local SP 3 Contact closure puts the controller
into local setpoint 3.
To Local SP 4 Contact closure puts the controller
into local setpoint 4.
To Direct Action Contact closure selects direct
controller action.
To Hold Contact closure suspends Setpoint
Program or Setpoint Ramp. When
contact reopens, the controller starts
from the Hold point of the
Ramp/Program unless the
Ramp/Program was not previously
started via the Run/Hold (Setup key
and Increment key). This selection
applies to either loop.
To PID Set 2 To PID2 —Contact closure selects
PID Set 2.
To PID Set 3 To PID2 —Contact closure selects
PID Set 3.
To PID Set 4 To PID2 —Contact closure selects
PID Set 4.
PV Source Input 2 Contact closure selects PV = Input 2.
Rerun Rerun allows the Setpoint
Programmer to be reset to the initial
segment of its current cycle, unit
stays in previous mode.
To Run Run —Contact closure starts a
stopped SP Ramp or Program. Upper
left character blinks “Run”.
Reopening the contact puts
controller in HOLD mode. This
selection applies to either loop.
Chapter 4 - Configuration