Function Prompt
Selections or Range
of Setting
Parameter Definition
within the range of
the selected variable
to represent the
minimum output (0
or 4 mA)
This is a value in engineering units
used to represent all Auxiliary
Output parameters except Output.
For Output, this is a value in percent
and can be any value between –5 %
and +105 %. However, keep in mind
that relay output types can only be
scaled 0 % to 100 %.
CO High Value High Scale Value
within the range of
the selected variable
to represent the
maximum output (20
mA)
Auxiliary Output High Scaling Factor
This is a value in engineering units
used to represent all Auxiliary Output
parameters except Output.
For Output, this is a value in percent
and can be any value between –5 %
and +105 %. However, keep in mind
that relay output types can only be
scaled 0 % to 100 %.
DI 1 Function Digital Input 1 Selections —All
selections are available for Input 1.
The controller returns to its original
state when contact opens, except
when overruled by the keyboard.
None No Digital Input Selections.
To Manual Contact closure puts the affected
loop into manual mode. Contact
open returns controller to former
mode.
To Local SP 1 When a remote setpoint is
configured, contact closure puts the
controller into local setpoint 1. When
contact opens, the controller returns
to former operation—local or remote
setpoint—unless SP Select key is
pressed while digital input is active.
If this happens, the controller will
stay in the local setpoint mode when
contact opens.
141