Function
Prompt
Selections or
Range of
Setting
Parameter Definition
Ethernet Ethernet —Enables Ethernet communication port.
Modbus
Address
1 to 99 Communications station address —This is a number
that is assigned to a controller that is to be used with
the communications option. This number will be its
address.
Baud Rate Baud Rate is the transmission speed in bits per
second. This value is used for RS-485.
4800 4800 BAUD
9600 9600 BAUD
19200 19200 BAUD
38400 38400 BAUD
Response
Delay
1 to 500
milliseconds
Response Delay —Configurable response-delay timer
allows you to force the instrument to delay its
response for a time period of from 1 to 500
milliseconds compatible with the host system
hardware/software.
Word Order
for Float
Defines word/byte order of floating point data for
communications. Byte values:
0 1 2 3
seeeeee
e
emmmmm
mm
mmmmmm
mm
mmmmmm
mm
Where:
s = sign, e = exponent, m = mantissa bit
FP_B
0 1 2 3
FP_BB
1 0 3 2
FP_L
3 2 1 0
FP_LB
2 3 0 1
Ethernet
Address
0.0.0.0 to
255.255.255.2
55
Ethernet address, ranging from 0.0.0.0 to
255.255.255.255. It only applies to Ethernet
communication port.
149
Chapter 4 - Configuration