EasyManuals Logo

Honeywell UDC2800 User Manual

Honeywell UDC2800
432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #154 background imageLoading...
Page #154 background image
154
Function
Prompt
Selections or Range
of Setting
Parameter Definition
Note 1: This Deviation Alarm is based upon deviation from whichever SP is active.
Note 2: Alarm 1 is not available if the Timer is enabled because Alarm 1 is dedicated to
Timer output.
Note 3: Loop Break monitors the control loop to determine if it is working. When
enabled, the control output is checked against the minimum and maximum output
limit settings. When the output reaches one of these limits, a timer begins. If the timer
expires and the output has not caused the PV to move by a pre-determined amount,
then the alarm activates, thus signalling that the loop is broken. The loop break timer
value must be configured by the operator as the AxSx VAL entry. This value is in
seconds with a range of 0 to 3600 seconds. A setting of 0 is equivalent to an
instantaneous loop break when the output reaches one of its limit values.
The amount of PV Movement required is determined by the “UNITS” setting in the
Display Setup Group. For the Degrees F configuration, the PV must move by 3 ° in the
desired direction in the time allowed. For the Degrees C configuration, the PV must
move by 2 ° in the desired direction in the time allowed. For the “NONE” selection, the
PV must move 1% of the PV range in the time allowed.
Loop Break alarms do not have a HIGH/LOW State configuration, they are always
assumed to be a HIGH state alarm.
Note 4: Thermocouple Warning means that the instrument has detected that the
Thermocouple Input is starting to fail. Not valid for other input types.
Note 5: Thermocouple Failing means that the instrument has detected that the
Thermocouple Input is in imminent danger of failing. Not valid for other input types.
Note 6: Alarm is triggered when the current SP is remote setpoint.
Note 7:
Event On: Alarm is set to on when the alarm (event) condition is met.
Event Off: Alarm is set as off when the alarm (event) condition is met.
NOTE: The alarm will not be reset after the event is finished.
Note 8: When the controller is configured for Three Position Step Control, alarms set for
Output will not function.
A1S1 Value Value in engineering
units
Alarm 1 Setpoint 1 Value —This is the value
at which you want the alarm type chosen in
Chapter 4 - Configuration

Table of Contents

Other manuals for Honeywell UDC2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC2800 and is the answer not in the manual?

Honeywell UDC2800 Specifications

General IconGeneral
Control ModesPID, ON/OFF, Manual
MountingPanel Mount
DisplayDual 4-digit LED
Input TypesThermocouple, RTD, mA, mV, V
Output TypesRelay
Power Supply100-240 VAC, 50/60 Hz
CommunicationRS-485 Modbus RTU
Enclosure RatingNEMA 4X

Related product manuals