Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex Decimal
SP Program 1 81C 2076 INT
R/W
0 = Disabled
1 = Enabled
Start Segment 81D 2077 INT
R/W
Ramp segment
1 to 8
End Segment 81E 2078 INT
R/W
Soak segment
0 = Soak 8
1 = Soak 6
2 = Soak 4
3 = Soak 2
Ramp Unit 81F 2079 INT
R/W
0 = Time Hrs:Mins
1 = Rate EU/Min
2 = Rate EU/Hr
Recycles 820 2080 INT
R/W
0 to 100
Segment 1
Ramp
24 36 FP
R/W
00:00 ~ 99.59 (0-99 Hrs:0
-59Min)or
0 to 999 (EU/Min) or 0 to 999
(EU/Hr)
Segment 2 SP 25 37 FP
R/W
Within Setpoint Limits
Segment 2 Time 26 38 FP
R/W
00:00 ~ 99.59 (0-99 Hrs:0
-59Mins)
Segment 3
Ramp
27 39 FP
R/W
00:00 ~ 99.59 (0-99 Hrs:0
-59Min)or
0 to 999 (EU/Min) or 0 to 999
(EU/Hr)
Segment 4 SP 28 40 FP
R/W
Within Setpoint Limits
Segment 4 Time 29 41 FP
R/W
00:00 ~ 99.59 (0-99 Hrs:0
-59Mins)
Segment 5
Ramp
2A 42 FP
R/W
00:00 ~ 99.59 (0-99 Hrs:0
-59Min)or
0 to 999 (EU/Min) or 0 to 999
(EU/Hr)
335
Chapter 11 - Modbus RTU Function Codes 20&21