SP Ramp/Rate/Program
Table below lists all the register addresses and ranges or selections
for the function parameters in Set-up Group SP Ramp/Program.
Table 11-16: Set-up Group Setpoint Ramp/Program
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex Decimal
SP Ramp
Function
815 2069 INT
R/W
0 = Disabled
1 = Enabled
Ramp Time Min 20 32 FP
R/W
0 to 255 (minutes)
Ramp Final SP 1F 31 FP
R/W
SP High/Low limit in Control
setup group.
SP Rate
Function
816 2070 INT
R/W
0 = Disabled
1 = Enabled
Rate Up EU/Hr 21 33 FP
R/W
0 to 9999
Rate Down
EU/Hr
22 34 FP
R/W
0 to 9999
SP Program
Function
817 2071 INT
R/W
0 = Disabled
1 = Enabled
Soak Deviation 23 35 FP
R/W
0 to 99.9
0 = disable soak deviation
function
Program
Termination
818 2072 INT
R/W
0 = Last Setpoint and Mode
1 = Manual, Failsafe Output
Program End
State
819 2073 INT
R/W
0 = Disable SP Program
1 = Hold at Program End
Key Reset/Rerun 81A 2074 INT
R/W
0 = Disable
1 = To Begin
2 = Rerun
Hot Start 81B 2075 INT
R/W
0 = Disabled
1 = Enabled
Chapter 11 - Modbus RTU Function Codes 20&21