Parameter
Description
Register Address
Data
Type
Access
Data Range or Enumerated
Selection
Hex Decimal
1 = Rate EU/Mins
2 = Rate EU/Hrs
Recycles 82D 2093 INT
R/W
0 to 100
Segment 1 Ramp 33 51 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
or
0 to 999 (Degrees/Minute)
Segment 2 SP 34 52 FP
R/W
Within Setpoint Limits
Segment 2 Time 35 53 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
Segment 3 Ramp 36 54 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
or
0 to 999 (Degrees/Minute)
Segment 4 SP 37 55 FP
R/W
Within Setpoint Limits
Segment 4 Time 38 56 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
Segment 5 Ramp 39 57 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
or
0 to 999 (Degrees/Minute)
Segment 6 SP 3A 58 FP
R/W
Within Setpoint Limits
Segment 6 Time 3B 59 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
Segment 7 Ramp 3C 60 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
or
0 to 999 (Degrees/Minute)
Segment 8 SP 3D 61 FP
R/W
Within Setpoint Limits
Segment 8 Time 3E 62 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
SP Program 3
Table below lists all the register addresses and ranges or selections
for the function parameters in Set-up Group SP Program 3.
337
Chapter 11 - Modbus RTU Function Codes 20&21