Table 11-18: Set-up Group Setpoint Program 3
Parameter
Description
Register Address
Data
Type
Access
Data Range or Enumerated
Selection
Hex Decimal
SP Program 3 833 2099 INT
R/W
0 = Disabled
1 = Enabled
Start Segment 834 2100 INT
R/W
Ramp segment
1 to 8
End Segment 835 2101 INT
R/W
Soak segment
0 = Soak 8
1 = Soak 6
2 = Soak 4
3 = Soak 2
Ramp Unit 836 2102 INT
R/W
0 = Time Hrs:Mins
1 = Rate EU/Mins
2 = Rate EU/Hrs
Recycles 837 2103 INT
R/W
0 to 100
Segment 1 Ramp 47 71 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
or
0 to 999 (Degrees/Minute)
Segment 2 SP 48 72 FP
R/W
Within Setpoint Limits
Segment 2 Time 49 73 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
Segment 3 Ramp 4A 74 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
or
0 to 999 (Degrees/Minute)
Segment 4 SP 4B 75 FP
R/W
Within Setpoint Limits
Segment 4 Time 4C 76 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
Segment 5 Ramp 4D 77 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
or
0 to 999 (Degrees/Minute)
Segment 6 SP 4E 78 FP
R/W
Within Setpoint Limits
Segment 6 Time 4F 79 FP
R/W
99.59 (0-99 Hrs:0 -59Min)
Chapter 11 - Modbus RTU Function Codes 20&21