Parameter
Description
Register Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex Decimal
SW Failsafe
Value
8AE 2222 INT
R/W
0 =0 Percent
1 = 100 Percent
Preset Manual
Output
F1 241 FP
R/W
0.0 to 100.0% of Output
Preset Auto
Output
F2 242 FP
R/W
0.0 to 100.0% of Output
Proportion Unit 8AF 2223 INT
R/W
0 = Proportional Band
1 = Gain
Reset Unit 8B0 2224 INT
R/W
0 = Repeats/Minute
1 = Minutes/Repeat
Options
Table below lists all the register addresses and ranges or selections
for the function parameters in Set-up Group Options.
Table 11-30: Set-up Group Options
Parameter
Description
Register
Address
Data
Type
Access
Data Range or Enumerated
Selection
Hex Decimal
Auxiliary
Output *
8B7 2231 INT
R/W
0 = Disable
1 = Input 1
2 = Input 2
3 = PV
4 = Deviation
5 = Output
6 = SP
7 = Local SP 1
8 = Local SP 2
363
Chapter 11 - Modbus RTU Function Codes 20&21

Table of Contents