364
Parameter
Description
Register
Address
Data
Type
Access
Data Range or Enumerated
Selection
Hex Decimal
9 = Local SP 3
10 = Local SP 4
11 = Remote SP
12 = Input Algorithm 1
CO Low Value FB 251 FP
R/W
Within the range of the
selected variable in ID 134
CO High Value FC 252 FP
R/W
Within the range of the
selected variable in ID 134
CO Range 8B8 2232 INT
R/W
0 = 4-20 mA
1 = 0-20 mA
Digital Input 1
Function
8B9 2233 INT
R/W
0 = None
1 = To Manual
2 = To Local Setpoint 1
3 = To Local Setpoint 2
4 = To Local Setpoint 3
5 = To Local Setpoint 4
6 = To Direct Action
7 = To Hold Ramp
8 = To PID Set 2
9 = To PID Set 3
10 = To PID Set 4
11 = PV Source Input 2
12 = Rerun SPP Cycle
13 = To Run Ramp
Chapter 11 - Modbus RTU Function Codes 20&21