Parameter Description
Register Address
Access Description
Hex Decimal
Alarm #1 SP #2 005C 40093
R/W Floating Point in
Engineering Units.
Gain #2 (Prop Band #2 if
active)
0060 40097
R/W Floating Point
Deadband 0062 40099
R/W Floating Point
Reset #2 0064 40101
R/W Floating Point in
Repeats/Minute or
Minutes/Repeat.
Rate #2 0066 40103
R/W Floating Point in Minutes
Cycle Time #2 0068 40105
R/W Floating Point in
Seconds.
LSP #1 006A 40107
R/W Floating Point in
Engineering Units.
LSP #2 006C 40109
R/W Floating Point in
Engineering Units.
Alarm #2 SP #1 006E 40111
R/W Floating Point in
Engineering Units.
Alarm #2 SP #2 0070 40113
R/W Floating Point in
Engineering Units.
SP Low Limit 0074 40117
R/W Floating Point in
Engineering Units.
SP High Limit 0076 40119
R/W Floating Point in
Engineering Units.
Working Set Point 0078 40121
R/W Floating Point in
Engineering Units.
Output Low Limit 007A 40123
R/W Floating Point in
Engineering Units.
Output High Limit 007C 40125
R/W Floating Point in
Engineering Units.
Output Working Value 007E 40127
R/W Floating Point in
Engineering Units.
PV Override Value 0080 40129
R/W Floating Point in
387
Chapter 12 - Standard Modbus Read, Write and Override Parameters