Figure 3-9: Dual Electromechanical Relay Option Output
Item Description
1 Dual Electromechanical relays are rated at 2 Amps @125 Vac or 250 Vac or 30
Vdc. Customer should size fuses accordingly. Use Fast Blow fuses only.
2 Electromechanical relays are rated at 5 Amps @ 125 Vac or 250 Vac or 30 Vdc.
Users should size fuses accordingly. Use Fast Blow fuses only.
See the table Universal Output Functionality and Restrictions for
relay terminal connections for other Output Algorithm Types.
Figure 3-10: Current Output
Item Description
1 When the instrument has the Current Output as shown, no Alarms are available
when using the Time Proportional Duplex or Three Position Step Control
Output Algorithms, as these outputs require both available relays.
2 Electromechanical relays are rated at 5 Amps @ 125 Vac or 250 Vac or 30 Vdc.
Users should size fuses accordingly. Use Fast Blow fuses only.
61
Chapter 3 - Installation